Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 28, 2016, 06:36 AM
  • E 0028_E 0027_20161027_235239.mp4

Date
10/27/2016
W/O
597390
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00028
PipeID
P07611
Time
11:36 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3866
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
V
Project
WO_597390_TV01088_OCT2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
E 0027
Downstream MH
E 0028
Dir. of Survey
Upstream
Length Surveyed
254.5 ft.
Total Length
254.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole E 0027 to E 0028
MH: E 0027MH: E 0028upstream0 ft. OBN - Obstacles Construction Debris, 25 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - MAGNESIUM COATING FINISH0 ft. OBN - Obstacles Construction Debris, 15 %of cross sectional area, from 04 to 08 o'clock, Finish0 ft. MSA - Survey Abandoned - SEVERE DEBRIS 25%154.9 ft. OBN - Obstacles Construction Debris, 15 %of cross sectional area, from 04 to 08 o'clock, Start - NOT VISIBLE191.8 ft. SAV - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES252.4 ft. MGO - General Observation - MAGNESIUM COATING START252.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start254.5 ft. MGO - Reversal Inspection254.5 ft. MWM - Water Mark, 20 %of cross sectional area254.5 ft. MGO - General Observation - ROACHES IN MH254.5 ft. MWL - Water Level, 15 %of cross sectional area254.5 ft. AMH - Downstream Manhole, Survey Begins - E 0027

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES

    62.7 ft. - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    254.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Survey Abandoned - SEVERE DEBRIS 25%

    254.5 ft. - Survey Abandoned - SEVERE DEBRIS 25%

Observations (14)

DistanceCodeObservation
2.1MGOMAGNESIUM COATING START
62.7SAV
0MGO
99.6OBNNOT VISIBLE
254.5OBNNOT VISIBLE
254.5SAP
254.5MGOMAGNESIUM COATING FINISH
0MWM
254.5OBN
254.5MSASEVERE DEBRIS 25%
0MGOROACHES IN MH
0MWL
0AMHE 0027
2.1SAP

Properties (5)

additional_info
SC301946
custom_field_two
4
customer
LACSD
datetime
2016-10-27T23:36:13-07:00
sewer_category