Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2016, 09:05 AM
  • 32 0131_32 0130_10272016_020542.mp4

Date
10/27/2016
W/O
592230
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19877
Time
2:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3795
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_592230_TV32048_SEP2016
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0131
Downstream MH
32 0130
Dir. of Survey
Downstream
Length Surveyed
473.4 ft.
Total Length
473.4 ft.
Structural Index
3
Structural Quick
3R00
Structural Rating
282
O&M Index
2
O&M Quick
412R
O&M Rating
192
Overall Index
3
Overall Quick
Overall Rating
474
Pipe schematic from manhole 32 0131 to 32 0130
MH: 32 0131MH: 32 0130downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01310 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COATING 90%2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start471.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish471.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish473.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE473.4 ft. AMH - Downstream Manhole, Survey Ends - 32 0130

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    473.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
2MGOMAG COATING 90%
0AMH32 0131
473.4MGOCOCKROACHES IN MANHOLE
471.5DAGS
0MWM
2DAGS
473.4AMH32 0130
471.5SAP
2SAP
0MWL

Properties (5)

additional_info
SC306333
custom_field_two
3
customer
LACSD
datetime
2016-10-27T02:05:25-07:00
sewer_category