Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2016, 07:39 AM
  • 32 0133_32 0132A_10272016_004009.mp4

Date
10/27/2016
W/O
592230
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19881
Time
12:39 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3795
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_592230_TV32048_SEP2016
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0133
Downstream MH
32 0132A
Dir. of Survey
Downstream
Length Surveyed
71.9 ft.
Total Length
71.9 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
2
O&M Quick
412B
O&M Rating
32
Overall Index
3
Overall Quick
Overall Rating
74
Pipe schematic from manhole 32 0133 to 32 0132A
MH: 32 0133MH: 32 0132Adownstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01330 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start70.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish70.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish71.9 ft. AMH - Downstream Manhole, Survey Ends - 32 0132A71.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2SAP
70.5SAP
70.5DAGS
0MWM
2MGOMAG COATING
71.9AMH32 0132A
2DAGS
71.9MGOCONNECTION AT MH 9 O'CLOCK
0AMH32 0133
0MWL

Properties (5)

additional_info
SC306333
custom_field_two
3
customer
LACSD
datetime
2016-10-27T00:39:38-07:00
sewer_category
Gravity