Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2016, 07:52 AM
  • 32 0132A_32 0132_10272016_005325.mp4

Date
10/27/2016
W/O
592230
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19880
Time
12:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3795
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_592230_TV32048_SEP2016
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0132A
Downstream MH
32 0132
Dir. of Survey
Downstream
Length Surveyed
402.9 ft.
Total Length
402.9 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
240
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
3
Overall Quick
Overall Rating
400
Pipe schematic from manhole 32 0132A to 32 0132
MH: 32 0132AMH: 32 0132downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 0132A0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 90%2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start401 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish401 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish402.9 ft. AMH - Downstream Manhole, Survey Ends - 32 0132

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH32 0132A
2SAP
401DAGS
0MWL
401SAP
0MWM
2MGOMAG COATING 90%
402.9AMH32 0132
2DAGS
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (5)

additional_info
SC306333
custom_field_two
3
customer
LACSD
datetime
2016-10-27T00:52:23-07:00
sewer_category
Gravity