Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2016, 07:11 AM
  • C 0675_C 0674 _28092016_001415.mp4

Date
09/28/2016
W/O
592158
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01114
PipeID
P23944
Time
12:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3591
Sewer Name
C JOINT OUTFALL C - UNIT 3H
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_592158_TV29041_SEP2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
C 0675
Downstream MH
C 0674
Dir. of Survey
Downstream
Length Surveyed
331 ft.
Total Length
331.1 ft.
Structural Index
3
Structural Quick
4234
Structural Rating
24
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
162
Pipe schematic from manhole C 0675 to C 0674
MH: C 0675MH: C 0674downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 06750 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 10 %of cross sectional area6.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start36.7 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES50.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"76.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES182.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES202.8 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES207 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"262.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES295.1 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES298.1 ft. FM - Fracture Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES300.5 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start319.8 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish324.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES331.1 ft. AMH - Downstream Manhole, Survey Ends - C 0674331.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK331.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (10)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock,  , within 8 inches of joint: YES, Start

    6.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    36.7 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    76.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    182.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    202.8 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    262.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    295.1 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES

    298.1 ft. - Fracture Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES

  • Deposits Settled Fine,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO, Start

    300.5 ft. - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    324.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
331.1AMHC 0674
298.1FM
0AMHC 0675
0MWL
76.5CM
331.1MGOCONNECTION AT MH 3 O'CLOCK
202.8CM
262.4CL
6.9DAE
295.1FM
324.6CL
182.1CM
50.8TF
36.7CM
0MGOCONNECTION AT MH 3 O'CLOCK
300.5DSF
207TF
331.1DAE
319.8DSF
0MWM

Properties (6)

additional_info
SC306186
custom_field_two
3
customer
LACSD
datetime
2016-09-28T00:11:31-07:00
sewer_category
Gravity
year_laid
37482