Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2016, 09:53 PM
  • 22 0890_22 0889 _09262016_030128.mp4

Date
08/19/2016
W/O
1576257
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00799
PipeID
P17260
Time
2:53 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3767
Sewer Name
22 CONEY TRUNK, SECTS 2&3
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
WO_592094_TV22030_SEP2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
22 0889
Downstream MH
22 0890
Dir. of Survey
Upstream
Length Surveyed
320.4 ft.
Total Length
320.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
128
Pipe schematic from manhole 22 0889 to 22 0890
MH: 22 0889MH: 22 0890upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 08902.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish320.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start320.4 ft. MWL - Water Level, 15 %of cross sectional area320.4 ft. MWM - Water Mark, 20 %of cross sectional area320.4 ft. AMH - Downstream Manhole, Survey Begins - 22 0889

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0DAGS
0MWL
320.4AMH22 0890
0MWM
0AMH22 0889
318DAGS

Properties (5)

additional_info
SC306302
custom_field_two
4
customer
LACSD
datetime
2016-08-19T14:53:02-07:00
sewer_category
Gravity