Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2016, 07:44 AM
  • 22 0550_22 0549 _09062016_010505.mp4

Date
09/06/2016
W/O
592045
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00791
PipeID
P16892
Time
12:44 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3423
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
WO_592045_TV22006_SEP2016
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0550
Downstream MH
22 0549
Dir. of Survey
Downstream
Length Surveyed
471 ft.
Total Length
471 ft.
Structural Index
3
Structural Quick
3R00
Structural Rating
279
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
281
Pipe schematic from manhole 22 0550 to 22 0549
MH: 22 0550MH: 22 0549downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05500 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 30 ft. VC - Vermin Cockroach2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"54 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"103.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"107.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"152.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"156.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"205.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"209.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"254.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"258.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"307.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"311.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"400.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"441.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"445.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"467.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish470.7 ft. MGO - General Observation - CONNECTION AT MH 9470.9 ft. VC - Vermin Cockroach471 ft. AMH - Downstream Manhole, Survey Ends - 22 0549

Observation photos (15)

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    50 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    54 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    103.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    107.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    152.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    156.4 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    205.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    209.4 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"

    254.3 ft. - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    258.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    307.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    311.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    400.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    441.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    445.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

Observations (25)

DistanceCodeObservation
103.2TFC
0MWM
152.6TFC
471AMH22 0549
2SAV
0AMH22 0550
311.6TFC
470.7MGOCONNECTION AT MH 9
50TFC
205.6TFC
0MWL
254.3TFC
307.1TFC
445.1TFC
54TF
400.7TF
258.3TFC
467.6SAV
470.9VC
156.4TFC
209.4TFC
107.1TF
0MGOCONNECTION AT MH 3
441.3TF
0VC

Properties (5)

additional_info
SC305986
custom_field_two
3
customer
LACSD
datetime
2016-09-06T00:44:21-07:00
sewer_category
Gravity