Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2016, 10:56 AM
  • 22 1407_22 0537 _09062016_035915.mp4

Date
09/06/2016
W/O
592045
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00791
PipeID
P16879
Time
3:56 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3423
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
WO_592045_TV22006_SEP2016
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1407
Downstream MH
22 0537
Dir. of Survey
Downstream
Length Surveyed
197.6 ft.
Total Length
197.6 ft.
Structural Index
3
Structural Quick
413G
Structural Rating
118
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
119
Pipe schematic from manhole 22 1407 to 22 0537
MH: 22 1407MH: 22 0537downstream0 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - CONNECTION AT MH 90 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 14072.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start7.8 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES13.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"17.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"66.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"70.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"73.3 ft. MGO - General Observation - MAG. H.OX 10% START119.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"123.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"160.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"164.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"194.6 ft. MGO - General Observation - MAG. H.OX 10% FINISH194.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish197.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0537

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    7.8 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    13.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    17.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    66.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    70.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • General Observation - MAG. H.OX 10% START

    73.3 ft. - General Observation - MAG. H.OX 10% START

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    119.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    123.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    160.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    164.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (19)

DistanceCodeObservation
0VC
194.6MGOMAG. H.OX 10% FINISH
13.2TFC
197.6AMH22 0537
194.6SAV
0MGOCONNECTION AT MH 9
0MWL
0MWM
0AMH22 1407
123.5TFC
160.1TF
164.2TFC
73.3MGOMAG. H.OX 10% START
7.8FM
17.2TFC
119.3TFC
2.9SAV
70.5TFC
66.7TF

Properties (5)

additional_info
SC305986
custom_field_two
3
customer
LACSD
datetime
2016-09-06T03:56:34-07:00
sewer_category
Gravity