Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2016, 06:28 AM
  • 22 0561_22 0560 _08292016_232856.mp4

Date
08/29/2016
W/O
592045
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00791
PipeID
P16903
Time
11:28 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3422
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
WO_592045_TV22006_SEP2016
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0561
Downstream MH
22 0560
Dir. of Survey
Downstream
Length Surveyed
376.7 ft.
Total Length
376.7 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 22 0561 to 22 0560
MH: 22 0561MH: 22 0560downstream0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05610 ft. MGO - General Observation - CONNECTION AT MH 30 ft. MWL - Water Level, 10 %of cross sectional area67.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start103.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"159.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"171.8 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 4", 2"174.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"195 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"204.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"225.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"265.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"285.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"337.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"370.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.7 ft. MGO - General Observation - CONNECTION AT MH 3376.7 ft. AMH - Downstream Manhole, Survey Ends - 22 0560376.7 ft. MGO - General Observation - CONNECTION AT MH 9

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    67.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    103.5 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    159.1 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 4", 2"

    171.8 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 4", 2"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    174.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    195 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    204.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    225.1 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    265.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    285.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    337.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (20)

DistanceCodeObservation
0VC
0MWM
159.1TF
225.1TF
204.5TFC
376.7MGOCONNECTION AT MH 3
0AMH22 0561
265.3TF
0MGOCONNECTION AT MH 3
376.7AMH22 0560
195TF
370.1SAV
67.5SAV
337.1TB
376.7MGOCONNECTION AT MH 9
174.9TFC
0MWL
285.5TFC
171.8TBI
103.5TF

Properties (5)

additional_info
SC305984
custom_field_two
3
customer
LACSD
datetime
2016-08-29T23:28:33-07:00
sewer_category
Gravity