Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2016, 09:21 AM
  • 22 0524_22 0523 _09082016_022236.mp4

Date
09/08/2016
W/O
592045
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00791
PipeID
P16864
Time
2:21 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3424
Sewer Name
22 BEN LOMOND TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
26
Purpose
Routine Assessment
Project
WO_592045_TV22006_SEP2016
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0524
Downstream MH
22 0523
Dir. of Survey
Downstream
Length Surveyed
283.6 ft.
Total Length
283.7 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
170
Pipe schematic from manhole 22 0524 to 22 0523
MH: 22 0524MH: 22 0523downstream0 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - CONNECTION AT MH 90 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05240 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 32 ft. MGO - General Observation - MAG. H.OX 20% START2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start31.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"35.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"84.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"88.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"133.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"136.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"185.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"189.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"238.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"242.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"280 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish280.4 ft. MGO - General Observation - MAG. H.OX 20% FINISH283.6 ft. MGO - General Observation - CONNECTION AT MH 9283.7 ft. VC - Vermin Cockroach283.7 ft. AMH - Downstream Manhole, Survey Ends - 22 0523

Observation photos (12)

  • General Observation - CONNECTION AT MH 9

    0 ft. - General Observation - CONNECTION AT MH 9

  • General Observation - CONNECTION AT MH 3

    0 ft. - General Observation - CONNECTION AT MH 3

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    31.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    35.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    84.4 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    88.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    133.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    136.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    185.8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    189.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    238.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    242.5 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (23)

DistanceCodeObservation
88.7TF
2MGOMAG. H.OX 20% START
280SAV
31.5TFC
0VC
280.4MGOMAG. H.OX 20% FINISH
283.6MGOCONNECTION AT MH 9
238.5TFC
35.6TFC
136.9TFC
242.5TF
0MGOCONNECTION AT MH 9
133.1TFC
283.7VC
185.8TFC
283.7AMH22 0523
0MWM
84.4TFC
2SAV
0AMH22 0524
0MWL
189.5TFC
0MGOCONNECTION AT MH 3

Properties (5)

additional_info
SC305988
custom_field_two
3
customer
LACSD
datetime
2016-09-08T02:21:59-07:00
sewer_category