Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2016, 05:03 AM
  • 22 0534A_22 0534 _09072016_220308.mp4

Date
09/07/2016
W/O
592045
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00791
PipeID
P16876
Time
10:03 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3424
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
WO_592045_TV22006_SEP2016
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0534A
Downstream MH
22 0534
Dir. of Survey
Downstream
Length Surveyed
260.9 ft.
Total Length
260.9 ft.
Structural Index
3
Structural Quick
3I2B
Structural Rating
179
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
181
Pipe schematic from manhole 22 0534A to 22 0534
MH: 22 0534AMH: 22 0534downstream0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 0534A2 ft. MGO - General Observation - MAG. H.OX 20% START5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"44.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"85.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"89.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"142.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"146.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"195.1 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Start200.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"244.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"248.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"257.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish258 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Finish258.1 ft. MGO - General Observation - MAG. H.OX 20% FINISH260.8 ft. VC - Vermin Cockroach260.9 ft. AMH - Downstream Manhole, Survey Ends - 22 0534

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    40.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    44.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    85.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    89.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    142.8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    146.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Water Level, Sag in pipe, 30 %of cross sectional area, Start

    195.1 ft. - Water Level, Sag in pipe, 30 %of cross sectional area, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    200.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    244.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    248.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (21)

DistanceCodeObservation
257.8SAV
258.1MGOMAG. H.OX 20% FINISH
260.9AMH22 0534
260.8VC
142.8TFC
89.6TFC
195.1MWLS
248.3TFC
44.6TFC
0VC
40.7TFC
0MWM
85.2TFC
0MWL
0AMH22 0534A
5SAV
258MWLS
244.6TFC
200.1TFC
146.6TFC
2MGOMAG. H.OX 20% START

Properties (5)

additional_info
SC305988
custom_field_two
3
customer
LACSD
datetime
2016-09-07T22:03:04-07:00
sewer_category