Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2017, 07:34 AM
  • 14 0242_14 0241 _02012017_233533.mp4

Date
02/01/2017
W/O
613594
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00569
PipeID
P18295
Time
11:34 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4228
Sewer Name
14 AVENUE "H" TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_613594_TV14037_JAN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
14 0242
Downstream MH
14 0241
Dir. of Survey
Downstream
Length Surveyed
605 ft.
Total Length
605 ft.
Structural Index
3
Structural Quick
3W2I
Structural Rating
456
O&M Index
2
O&M Quick
412W
O&M Rating
244
Overall Index
2
Overall Quick
Overall Rating
700
Pipe schematic from manhole 14 0242 to 14 0241
MH: 14 0242MH: 14 0241downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 02420 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - MAG COATING 75%0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start365.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start603.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish603.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish603.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish605 ft. AMH - Downstream Manhole, Survey Ends - 14 0241

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    365.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
603.1DAGS
603.1SSS
0AMH14 0242
603.1SAP
2SAP
2DAGS
365.2SSS
605AMH14 0241
0MWM
0MGOMAG COATING 75%
0MWL

Properties (4)

additional_info
SC306730
custom_field_two
3
customer
LACSD
datetime
2017-02-01T23:34:51-08:00