Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2017, 08:16 AM
  • 02 1710_02 1709_01052017_001654.mp4

Date
01/05/2017
W/O
613349
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00289
PipeID
P18873
Time
12:16 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4050
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
06
Purpose
Routine Assessment
Project
WO_613349_TV02103_JAN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1710
Downstream MH
02 1709
Dir. of Survey
Downstream
Length Surveyed
338.1 ft.
Total Length
338.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
134
Pipe schematic from manhole 02 1710 to 02 1709
MH: 02 1710MH: 02 1709downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17100 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start27.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"30.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"91 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"156.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"215 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"334.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"336 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish336 ft. MGO - General Observation - COCKROACHES IN MANHOLE338.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1709338.1 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    336 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
275.5TFC
137.5TBA
156.8TFC
216.9TFA
0MWL
0AMH02 1710
338.1AMH02 1709
2DAGS
108.5TBA
30.6TFA
215TBA
94.3TFC
27.6TFA
0MGOCOCKROACHES IN MANHOLE
153.9TFA
334.7TFA
336DAGS
91TFC
0MWM
336MGOCOCKROACHES IN MANHOLE
220.4TFC
338.1MGOCAPPED CONNECTION AT MH 3 O'CLOCK
278.4TFA

Properties (5)

additional_info
SC306448
custom_field_two
4
customer
LACSD
datetime
2017-01-05T00:16:30-08:00
sewer_category