Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2016, 10:14 AM
  • 16 0263_16 0262 _10052016_031431.mp4

Date
10/05/2016
W/O
592155
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00652
PipeID
P13310
Time
3:14 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3774
Sewer Name
16 CHAPEL AVENUE TRUNK, SECTION 1
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_592155_TV16001_SEP2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0263
Downstream MH
16 0262
Dir. of Survey
Downstream
Length Surveyed
244.7 ft.
Total Length
244.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 16 0263 to 16 0262
MH: 16 0263MH: 16 0262downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 02630 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.2 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES79.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"103 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"139 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish242.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0262

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    62.2 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
156.3TFA
242.5DAGS
0AMH16 0263
244.7AMH16 0262
103TFC
206.9TFA
174.6TFC
242.5TFC
79.4TFC
0MWL
2DAGS
139TFC
180.2TFC
126.9TFA
7.3TFC
105.7TFA
28.1TFA
227.6TFC
62.2CS
0MWM
215.5TFA
55.7TFA

Properties (5)

additional_info
SC306311
custom_field_two
4
customer
LACSD
datetime
2016-10-05T03:14:28-07:00
sewer_category
Gravity