Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 6, 2016, 11:11 AM
  • 02 1552_02 1551_12062016_032734.mp4

Date
12/06/2016
W/O
607654
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00230
PipeID
P03984
Time
3:11 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3932
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
EAST LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_607654_TV02006_DEC2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1551
Downstream MH
02 1552
Dir. of Survey
Upstream
Length Surveyed
210.1 ft.
Total Length
210.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1551 to 02 1552
MH: 02 1551MH: 02 1552upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 15520.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish9.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"13.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"23.5 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"25.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"36.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"62.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"79 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"80.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"107.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"127.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"130.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"161.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"178.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"182.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"208.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start210.1 ft. AMH - Downstream Manhole, Survey Begins - 02 1551210.1 ft. MWM - Water Mark, 25 %of cross sectional area210.1 ft. MWL - Water Level, 5 %of cross sectional area210.1 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
209.2DAGS
0AMH02 1551
103TFC
2DAGS
147.3TFA
131.1TFC
0MWM
31.2TFC
48.7TF
129.2TF
196.4TFC
28TFC
200.6TBA
173.7TFC
186.6TBA
0MWL
80TFC
0MGOLATERAL AT MH 9 O CLOCK
210.1AMH02 1552
82.2TFC
184.7TFC

Properties (5)

additional_info
SC307676
custom_field_two
4
customer
LACSD
datetime
2016-12-06T03:11:00-08:00
sewer_category
Gravity