Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2016, 11:12 AM
  • 05 0820_05 0819 _11282016_031234.mp4

Date
11/28/2016
W/O
602600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00419
PipeID
P06050
Time
3:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4022
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
WO_602600_TV05009_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0820
Downstream MH
05 0819
Dir. of Survey
Downstream
Length Surveyed
288.6 ft.
Total Length
288.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
116
Pipe schematic from manhole 05 0820 to 05 0819
MH: 05 0820MH: 05 0819downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 08200 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start33.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"36.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"83.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"86.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - CAPPED WITH A HOLE/VOID137.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"194 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish286.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE288.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0819288.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK288.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - CAPPED WITH A HOLE/VOID

    86.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - CAPPED WITH A HOLE/VOID

  • General Observation - COCKROACHES IN MANHOLE

    286.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
286.7DAGS
288.6AMH05 0819
194TFC
248.3TFC
191.7TFA
288.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK
288.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
36.2TFC
33.3TFA
245.9TFA
137.5TFA
0MWL
86.1TFDCAPPED WITH A HOLE/VOID
0AMH05 0820
83.6TFA
0MWM
286.7MGOCOCKROACHES IN MANHOLE
2DAGS
140.2TFC

Properties (5)

additional_info
SC306414
custom_field_two
4
customer
LACSD
datetime
2016-11-28T03:12:14-08:00
sewer_category
Gravity