Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2016, 09:34 AM
  • 05 0826_05 0825 _11282016_013526.mp4

Date
11/28/2016
W/O
602600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00419
PipeID
P06056
Time
1:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4022
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
WO_602600_TV05009_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0825
Downstream MH
05 0826
Dir. of Survey
Upstream
Length Surveyed
351 ft.
Total Length
351 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
138
Pipe schematic from manhole 05 0825 to 05 0826
MH: 05 0825MH: 05 0826upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 05 08262.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish15.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"17.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"69 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"123 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"349 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start351 ft. MWL - Water Level, 15 %of cross sectional area351 ft. AMH - Downstream Manhole, Survey Begins - 05 0825351 ft. MGO - General Observation - COCKROACHES IN MANHOLE351 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK351 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    351 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
171.2TFA
348.9DAGS
0MWL
279.3TFA
351MGOCOCKROACHES IN MANHOLE
173.7TFA
95.3TFC
351MGOACTIVE CONNECTION AT MH 9 O'CLOCK
333.3TFA
0AMH05 0825
2DAGS
228TFA
0MGOCOCKROACHES IN MANHOLE
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
282TFA
92.5TFC
0MWM
351AMH05 0826
225.2TFA
335.9TFA

Properties (5)

additional_info
SC306414
custom_field_two
4
customer
LACSD
datetime
2016-11-28T01:34:35-08:00
sewer_category