Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2016, 11:13 AM
  • 05 0811_05 0810 _12022016_031329.mp4

Date
12/02/2016
W/O
602600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00419
PipeID
P06042
Time
3:13 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4026
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
HOLLY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
WO_602600_TV05009_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0811
Downstream MH
05 0810
Dir. of Survey
Downstream
Length Surveyed
280.7 ft.
Total Length
280.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2K1H
O&M Rating
164
Overall Index
2
Overall Quick
Overall Rating
166
Pipe schematic from manhole 05 0811 to 05 0810
MH: 05 0811MH: 05 0810downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 08110 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS12.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.8 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR54.1 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR59.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS62.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.4 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR75.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start109.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS111.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.7 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES159.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS162 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.7 ft. RTJ - Roots Tap Joint, from 08 to 12 o'clock, 15 %, within 8 inches of joint: YESR261.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish278.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish280.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK280.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE280.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0810

Observation photos (13)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    9.5 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

    49.8 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

    54.1 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS

    59.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    67.4 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    75.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS

    109.4 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS

  • Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    141.7 ft. - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS

    159.3 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - SEVERE ROOTS

  • Roots Tap Joint, from 08 to 12 o'clock, 15 %, within 8 inches of joint: YESR

    257.7 ft. - Roots Tap Joint, from 08 to 12 o'clock, 15 %, within 8 inches of joint: YESR

  • General Observation - COCKROACHES IN MANHOLE

    280.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (27)

DistanceCodeObservation
211.9TFC
280.7MGOACTIVE CONNECTION AT MH 9 O'CLOCK
141.7CS
9.5TFDROOTS
280.7MGOCOCKROACHES IN MANHOLE
280.7AMH05 0810
111.7TFC
67.4RFJ
75.2RFJ
159.3TFDSEVERE ROOTS
261.4TFC
62.4TFC
162TFC
0AMH05 0811
0MGOCOCKROACHES IN MANHOLE
0MWM
2DAGS
12.3TFC
0MWL
49.8RFJ
257.7RTJ
54.1RFJ
278.5DAGS
59.6TFDSEVERE ROOTS
278.5RFJ
209.1TFC
109.4TFDSEVERE ROOTS

Properties (5)

additional_info
SC306418
custom_field_two
4
customer
LACSD
datetime
2016-12-02T03:13:08-08:00
sewer_category