Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2016, 09:56 AM
  • 05 0825_05 0824 _11282016_015706.mp4

Date
11/28/2016
W/O
602600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00419
PipeID
P06055
Time
1:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4022
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
WO_602600_TV05009_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0825
Downstream MH
05 0824
Dir. of Survey
Downstream
Length Surveyed
281.5 ft.
Total Length
281.5 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
2
Overall Quick
Overall Rating
254
Pipe schematic from manhole 05 0825 to 05 0824
MH: 05 0825MH: 05 0824downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 08250 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.7 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES8.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"43.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES50.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start56.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"116.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"167 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE279.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish279.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0824281.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    7.7 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    43.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    50.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    279.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
0MWL
225.5TFC
0AMH05 0825
7.7CM
281.5AMH05 0824
281.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
116.9TFA
50.7CM
56.1TFC
2DAGS
114.1TFC
8.7TFC
58.4TFA
222.7TFC
279.2MGOCOCKROACHES IN MANHOLE
43.1CM
167TFC
279.2DAGS
279.2CM
164.4TFA
0MWM

Properties (5)

additional_info
SC306414
custom_field_two
3
customer
LACSD
datetime
2016-11-28T01:56:25-08:00
sewer_category