Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2016, 03:50 PM
  • H 0950_H 0949_20160216_090457.mp4

Date
02/16/2016
W/O
552579
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z01005
PipeID
P15363
Time
7:50 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3181
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
34
Purpose
Routine Assessment
Project
WO_552579_TV21022_FEB2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0950
Downstream MH
H 0949
Dir. of Survey
Downstream
Length Surveyed
250.9 ft.
Total Length
250.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 0950 to H 0949
MH: H 0950MH: H 0949downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 09500 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MGO - General Observation - MAGNEZIUM H.O COATING 50% start151.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"218.9 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: YES247.4 ft. MGO - General Observation - MAGNEZIUM H.O COATING 50% finish250.9 ft. AMH - Downstream Manhole, Survey Ends - H 0949

Observation photos (1)

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: YES

    218.9 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0AMHH 0950
247.4MGOMAGNEZIUM H.O COATING 50% finish
2MGOMAGNEZIUM H.O COATING 50% start
250.9AMHH 0949
0MWM
151.3TF
0MWL
218.9SSS

Properties (5)

additional_info
SC224996
custom_field_two
4
customer
LACSD
datetime
2016-02-16T07:50:11-08:00
sewer_category
GRAVITY