Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2016, 05:55 AM
  • 02 0110_02 0110_110116_232532.mp4

Date
11/01/2016
W/O
602602
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00237
PipeID
P02277
Time
10:55 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3754
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER, CA
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_602602_TV02019_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0110
Downstream MH
02 0109
Dir. of Survey
Downstream
Length Surveyed
336.3 ft.
Total Length
336.3 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
28
O&M Index
2
O&M Quick
312L
O&M Rating
135
Overall Index
2
Overall Quick
Overall Rating
163
Pipe schematic from manhole 02 0110 to 02 0109
MH: 02 0110MH: 02 0109downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01100 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES, Start19.5 ft. MWL - Water Level, 10 %of cross sectional area25.6 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES47.1 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES72.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - W/ CALCIUM82.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES86.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"95.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"122.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"145.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"172.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"184.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"199 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"219.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"225.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"240.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"250.6 ft. CC - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES262.3 ft. CC - Crack Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES267.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4", 3"268 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES276.1 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES279.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"279.9 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES292.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - W/ FRACTURES317.9 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES330.1 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES330.1 ft. B - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES333 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES, Finish336.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK336.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0109

Observation photos (14)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock,  , within 8 inches of joint: YES, Start

    7 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES

    25.6 ft. - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    47.1 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    82.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    250.6 ft. - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES

    262.3 ft. - Crack Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4", 3"

    267.5 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4", 3"

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    268 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 20 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    276.1 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    279.9 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    317.9 ft. - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    330.1 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

    330.1 ft. - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (35)

DistanceCodeObservation
336.2MGOCONNECTION AT MH 3 O'CLOCK
279.9CM
330.1FM
7CM
19.5MWL
47.1CM
82.5FL
330.1B
333DAGS
25.6CC
336.3AMH02 0109
276.1DAGS
172.8TFA
0MWL
199TFC
0AMH02 0110
225.5TFC
240.2TFC
7DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
145.8TFC
72.4TFW/ CALCIUM
219.6TF
122.8TFC
279.3TFA
317.9CC
250.6CC
86.8TFA
184.1TFC
95.7TFA
268CM
267.5TFD
292.7TFW/ FRACTURES
0MWM
262.3CC

Properties (4)

additional_info
SC303746
custom_field_two
1
customer
LACSD
datetime
2016-11-01T22:55:02-07:00