Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2016, 11:27 AM
  • 02 1651_02 1827 _14112016_032825.mp4

Date
11/14/2016
W/O
602593
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00236
PipeID
P04177
Time
3:27 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3822
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_602593_TV02018_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1651
Downstream MH
02 1827
Dir. of Survey
Downstream
Length Surveyed
241.9 ft.
Total Length
242 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
78
Pipe schematic from manhole 02 1651 to 02 1827
MH: 02 1651MH: 02 1827downstream0 ft. MMC - Material Change, Concrete pipe (non-reinfored)0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 16510 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK113.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start241.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish242 ft. AMH - Downstream Manhole, Survey Ends - 02 1827

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    113.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MMC
113.2SAP
242AMH02 1827
0MWL
0AMH02 1651
241.7SAP
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC304571
custom_field_two
3
customer
LACSD
datetime
2016-11-14T03:27:47-08:00