Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2016, 10:11 AM
  • 04 0076_04 0075_24022016_021148.mp4

Date
02/24/2016
W/O
552531
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11813
Time
2:11 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3265
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_552531_TV04009_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
15 in.
Upstream MH
04 0076
Downstream MH
04 0075
Dir. of Survey
Downstream
Length Surveyed
255.6 ft.
Total Length
255.6 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
150
O&M Index
2
O&M Quick
312S
O&M Rating
201
Overall Index
2
Overall Quick
Overall Rating
351
Pipe schematic from manhole 04 0076 to 04 0075
MH: 04 0076MH: 04 0075downstream0 ft. AMH - Upstream Manhole, Survey Begins - 04 00760 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area5.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start39.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"72.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.5 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES116.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"172.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"175.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"178 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"216.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET229.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"253.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish253.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE253.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish255.6 ft. AMH - Downstream Manhole, Survey Begins - 04 0075

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    18.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    98.5 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET

    219.6 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET

  • General Observation - COCKROACHES IN MANHOLE

    253.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
172.6TFA
216.8TFA
0AMH04 0076
253.8DAGS
219.6TFDOFFSET
72.3TFC
0DAGS
229.6TFC
5.7CM
39.3TFA
253.8CM
18.9DAE
175.1TFA
253.8MGOCOCKROACHES IN MANHOLE
90.5TFC
0MWM
0MWL
255.6AMH04 0075
98.5DAE
69.7TFA
253.8DAE
178TFA
116.2TFA

Properties (4)

additional_info
SC225488
custom_field_two
3
customer
LACSD
datetime