- Date
- 02/01/2016
- W/O
- 552384
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00157
- PipeID
- P10045
- Time
- 11:55 PM
- Certificate
- U-507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K3132
- Sewer Name
- D JOINT OUTFALL D - UNIT 6 RELIEF
- City
- LAWNDALE, CA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- WO_552384_TV05145_FEB2016
- Sewer Type
- GRAVITY
- Material
- Reinforced Concrete Pipe
- Lining Method
- Segmented Panel
- Shape
- Circular
- Height
- 39 in.
- Upstream MH
- D 0169
- Downstream MH
- D 0168
- Dir. of Survey
- Downstream
- Length Surveyed
- 736.5 ft.
- Total Length
- 736.5 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 2\00
- O&M Rating
- 292
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 292
Pipe schematic from manhole D 0169 to D 0168 Observation photos (2)

0 ft. - Water Mark, 35 %of cross sectional area

7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start