Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 09:17 AM
  • 02 1119_02 1998 _08112016_011852.mp4

Date
11/08/2016
W/O
602268
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02898
Time
1:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3818
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
WO_602268_TV02061_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1119
Downstream MH
02 1998
Dir. of Survey
Downstream
Length Surveyed
237.1 ft.
Total Length
237.1 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
138
Pipe schematic from manhole 02 1119 to 02 1998
MH: 02 1119MH: 02 1998downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11190 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area5.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start23.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"26.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"237.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1998237.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish237.1 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0AMH02 1119
0MWM
237.1AMH02 1998
104.5TF
26.4TF
127.1TFC
167.6TB
5.6CM
53.8TFC
80.8TF
237.1CM
237.1MGOCONNECTION AT MH 12 O'CLOCK
23.5TFC
0MWL

Properties (5)

additional_info
SC304567
custom_field_two
3
customer
LACSD
datetime
2016-11-08T01:17:27-08:00
sewer_category