Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2016, 10:56 AM
  • 02 1143_02 1142_07112016_025737.mp4

Date
11/07/2016
W/O
602268
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02927
Time
2:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3817
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
WO_602268_TV02061_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1143
Downstream MH
02 1142
Dir. of Survey
Downstream
Length Surveyed
316.1 ft.
Total Length
316.1 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
1
O&M Quick
411B
O&M Rating
20
Overall Index
3
Overall Quick
Overall Rating
194
Pipe schematic from manhole 02 1143 to 02 1142
MH: 02 1143MH: 02 1142downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11437.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES30.6 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES33.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start156.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - WITH ROOTS204.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.9 ft. RBL - Roots Ball Lateral, at 10 o'clock, 95 %233.1 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES236.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start256.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"309.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish312.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1142

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    7.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    30.6 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    33.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Ball Lateral, at 10 o'clock, 95 %

    204.9 ft. - Roots Ball Lateral, at 10 o'clock, 95 %

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    233.1 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    236.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    256.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
309.2TFC
33.3CM
30.6CM
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
236.7RFJ
312.3RFJ
312.3CM
7.9CM
156.2TFCWITH ROOTS
0MGOCONNECTION AT MH 9 O'CLOCK
233.1RFJ
316.1AMH02 1142
0MWL
204.9RBL
204.8TF
0AMH02 1143
256.9TFC

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2016-11-07T02:56:23-08:00
sewer_category