Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2016, 10:27 AM
  • 02 1144_02 1143_07112016_022903.mp4

Date
11/07/2016
W/O
602268
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02928
Time
2:27 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3817
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
WO_602268_TV02061_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1144
Downstream MH
02 1143
Dir. of Survey
Downstream
Length Surveyed
231.1 ft.
Total Length
231.1 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
135
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
135
Pipe schematic from manhole 02 1144 to 02 1143
MH: 02 1144MH: 02 1143downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11440 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area4.6 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES10.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"81 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish231 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED231 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK231.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1143

Observation photos (2)

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    4.6 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH02 1144
231MGOCONNECTION AT MH 3 O'CLOCK CAPPED
4.6CM
228.4CM
0MGOCONNECTION AT MH 3 O'CLOCK
0MWL
231MGOCONNECTION AT MH 9 O'CLOCK
0MWM
10.8CM
231.1AMH02 1143
81TFC
133.1TFC
28.1TFC

Properties (5)

additional_info
SC304566
custom_field_two
3
customer
LACSD
datetime
2016-11-07T02:27:58-08:00
sewer_category
Gravity