Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 10:35 AM
  • 01 0524_01 0523_08112016_023705.mp4

Date
11/08/2016
W/O
602233
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00206
PipeID
P01009
Time
2:35 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3874
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_602233_TV01017_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0524
Downstream MH
01 0523
Dir. of Survey
Downstream
Length Surveyed
317.5 ft.
Total Length
317.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0524 to 01 0523
MH: 01 0524MH: 01 0523downstream0 ft. MGO - General Observation - ROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 05240 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.3 ft. CM - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES27.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"29.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"74.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"76.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"124.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"127 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"174.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"177.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"224.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"227.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"258.3 ft. OBN - Obstacles Construction Debris, 15 %of cross sectional area, from 04 to 08 o'clock - NOT VISI BLE272.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"274.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"277.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"278 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"279.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"313.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish317.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0523317.5 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE317.5 ft. MGO - General Observation - ROACHES IN MH

Observation photos (17)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

    4.3 ft. - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    27.4 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    29.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    74.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    76.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    124.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    127 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    174.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    177.4 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    224.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    227.4 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    272.1 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    274.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    277.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    278 ft. - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    279.2 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

Observations (26)

DistanceCodeObservation
313.2DAGS
127TFC
317.5AMH01 0523
0MGOROACHES IN MH
4.3CM
0AMH01 0524
0MWL
274.7TFC
317.5MGOLATERAL AT MH 9 OCLOCK ACTIVE
27.4TFC
2.2DAGS
177.4TFC
278TFC
272.1TBA
29.5TFC
174.7TFC
76.7TF
279.2TB
317.5MGOROACHES IN MH
74.5TFC
124.6TFC
0MWM
258.3OBNNOT VISI BLE
227.4TFC
277.2TFC
224.9TFC

Properties (5)

additional_info
SC305204
custom_field_two
4
customer
LACSD
datetime
2016-11-08T02:35:58-08:00
sewer_category