Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 07:56 AM
  • 01 0529_01 0528_07112016_235634.mp4

Date
11/07/2016
W/O
602233
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00206
PipeID
P01016
Time
11:56 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3874
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_602233_TV01017_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0528
Downstream MH
01 0529
Dir. of Survey
Upstream
Length Surveyed
132.9 ft.
Total Length
132.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 01 0528 to 01 0529
MH: 01 0528MH: 01 0529upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 05290 ft. MGO - General Observation - ROACHES IN MH1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish11.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"32.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"59.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"107.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"130.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start132.9 ft. MGO - General Observation - ROACHES IN MH132.9 ft. MWL - Water Level, 10 %of cross sectional area132.9 ft. MWM - Water Mark, 15 %of cross sectional area132.9 ft. AMH - Downstream Manhole, Survey Begins - 01 0528

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    25.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    73.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    100.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    121 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

Observations (12)

DistanceCodeObservation
131.2DAGS
132.9AMH01 0529
0MGOROACHES IN MH
121TFC
25.7TFC
73.7TFC
2.3DAGS
0MWL
100.5TFC
0MWM
132.9MGOROACHES IN MH
0AMH01 0528

Properties (5)

additional_info
SC305204
custom_field_two
4
customer
LACSD
datetime
2016-11-07T23:56:01-08:00
sewer_category
Gravity