Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 7, 2017, 08:29 AM
  • 05 1104_05 1103_672017_013330.mp4

Date
06/07/2017
W/O
0635412
Weather
Dry
Operator/Surveyor
MARTIN,MANANES,REVELES
Sewer ID
Z00488
PipeID
P06339
Time
1:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0553
Sewer Name
05 MONETA EXTENSION TRUNK SECTION 1
City
CHENSHAW
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
20170602MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 1104
Downstream MH
05 1103
Dir. of Survey
Downstream
Length Surveyed
178.2 ft.
Total Length
178.2 ft.
Structural Index
2
Structural Quick
3127
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 05 1104 to 05 1103
MH: 05 1104MH: 05 1103downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - 10" VCP0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM0 ft. MWL - Water Level, 20 %of cross sectional area - STANDING WATER2.4 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SLIGHT5.5 ft. MGP - General Photograph - 10" VCP16.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT20.4 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL21.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open23.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL51.3 ft. MWL - Water Level, 50 %of cross sectional area51.3 ft. MGO - General Observation - CAMERA PARTIAL UNDER WATER START100.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H117.3 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL141.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL154.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H163 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped178 ft. MGO - General Observation - CAMERA PARTIAL UNDER WATER FINISH178.2 ft. MSA - Survey Abandoned - CAMERA UNDER WATER & SLUDGE

Observation photos (1)

  • General Photograph - 10" VCP

    5.5 ft. - General Photograph - 10" VCP

Observations (19)

DistanceCodeObservation
163TFCCapped
2.4FCSLIGHT
21.1TFOpen
51.3MWL
5.5MGP10" VCP
178.2MSACAMERA UNDER WATER & SLUDGE
51.3MGOCAMERA PARTIAL UNDER WATER START
141.7FCSL
0MWM
16.8FCSLIGHT
0MGO10" VCP
178MGOCAMERA PARTIAL UNDER WATER FINISH
0AMH1:30AM
117.3FCSL
0MWLSTANDING WATER
23.3FCSL
154.5FLH
20.4FCSL
100.7FCH

Properties (4)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2017-06-07T01:29:38-07:00