Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 6, 2017, 10:50 AM
  • 05 1106_05 1105_662017_051735.mp4

Date
06/06/2017
W/O
0635412
Weather
Dry
Operator/Surveyor
MARTIN,MANANES,REVELES
Sewer ID
Z00488
PipeID
P06341
Time
3:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0552
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
CHENSHAW
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
20170602MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 1106
Downstream MH
05 1105
Dir. of Survey
Downstream
Length Surveyed
339.5 ft.
Total Length
339.5 ft.
Structural Index
2
Structural Quick
332B
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
41
Pipe schematic from manhole 05 1106 to 05 1105
MH: 05 1106MH: 05 1105downstream0 ft. MWL - Water Level, 5 %of cross sectional area - NO FLOW0 ft. AMH - Upstream Manhole, Survey Begins - 5:15AM0 ft. MWM - Water Mark, 10 %of cross sectional area8 ft. MGO - General Observation - 10" VCP10.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT18.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE26.7 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H55.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H62 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active69.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H112.4 ft. MWL - Water Level, 2 %of cross sectional area118.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H118.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H131.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H143.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H151.7 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - H180.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL191.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H196.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped231.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL256 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H259.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL259.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H276.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL317 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H325.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active332 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H339.5 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM

Observation photos (1)

  • General Observation - 10" VCP

    8 ft. - General Observation - 10" VCP

Observations (28)

DistanceCodeObservation
332FCH
317FCH
180.1FCSL
256FLH
8MGO10" VCP
26.7FCH
276.4FCSL
62TFActive
196.9TFCCapped
0MWLNO FLOW
112.4MWL
18.8FLHAIRLINE
231.2FCSL
339.5AMH5:50AM
10.1FCSLIGHT
325.4TFActive
118.9FCH
69.9FCH
259.9FCSL
151.7FCH
0AMH5:15AM
259.9FCH
143.2FCH
55.2FCH
0MWM
191.9FCH
118.9FLH
131.3FCH

Properties (4)

custom_field_three
FEW FRACTURES
custom_field_two
4
customer
LACSD
datetime
2017-06-06T03:50:45-07:00