Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2016, 11:25 AM
  • 17 0034_17 0033_19022016_032535.mp4

Date
02/19/2016
W/O
552350
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00668
PipeID
P13757
Time
3:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3261
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Routine Assessment
Project
WO_552350_TV17001_FEB2016
Material
Vitrified Clay Pipe
Shape
Other
Height
21 in.
Upstream MH
17 0034
Downstream MH
17 0033
Dir. of Survey
Downstream
Length Surveyed
482.5 ft.
Total Length
482.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3227
O&M Rating
21
Overall Index
2
Overall Quick
Overall Rating
21
Pipe schematic from manhole 17 0034 to 17 0033
MH: 17 0034MH: 17 0033downstream0 ft. AMH - Upstream Manhole, Survey Begins - 17 00340 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start101.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS121 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS160.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS160.6 ft. RML - Roots Medium Lateral, from 10 to 12 o'clock, 10 %, within 8 inches of joint: YES201.2 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: YES201.2 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS256.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"307.3 ft. RFC - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES307.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS373.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"403.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"426.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"481.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish482.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK482.5 ft. AMH - Downstream Manhole, Survey Ends - 17 0033482.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (11)

  • Water Mark, 25 %of cross sectional area

    2 ft. - Water Mark, 25 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    101.4 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    121 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    160.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Lateral, from 10 to 12 o'clock, 10 %, within 8 inches of joint: YES

    160.6 ft. - Roots Medium Lateral, from 10 to 12 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: YES

    201.2 ft. - Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    201.2 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES

    307.3 ft. - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    307.3 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • General Observation - COCKROACHES IN MANHOLE

    482.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
2MWM
256.6TFA
160.6TFDROOTS
482.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
373.2TFC
121TFDROOTS
426.7TFC
101.4TFDROOTS
481.9DAGS
160.6RML
482.5AMH17 0033
307.3RFC
201.2RMC
307.3TFDROOTS
403.3TFC
2DAGS
201.2TFDROOTS
0AMH17 0034
0MWL
482.5MGOCOCKROACHES IN MANHOLE

Properties (5)

additional_info
SC225483
custom_field_two
4
customer
LACSD
datetime
2016-02-19T03:25:10-08:00
sewer_category