Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2016, 07:48 AM
  • 17 0038_17 0037_18022016_235003.mp4

Date
02/18/2016
W/O
552350
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00668
PipeID
P13761
Time
11:48 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3261
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Routine Assessment
Project
WO_552350_TV17001_FEB2016
Material
Vitrified Clay Pipe
Shape
Other
Height
24 in.
Upstream MH
17 0038
Downstream MH
17 0037
Dir. of Survey
Downstream
Length Surveyed
380.5 ft.
Total Length
380.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3424
O&M Rating
22
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole 17 0038 to 17 0037
MH: 17 0038MH: 17 0037downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00380 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start50.5 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS50.5 ft. RML - Roots Medium Lateral, from 12 to 02 o'clock, 5 %, within 8 inches of joint: YES69.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"99.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES158.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.7 ft. RFC - Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES219.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"224.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.2 ft. RFC - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES258.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.4 ft. RMC - Roots Medium Connection, from 12 to 05 o'clock, 30 %, within 8 inches of joint: YES293.4 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: YES293.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"379.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish380.5 ft. AMH - Downstream Manhole, Survey Ends - 17 0037380.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    50.5 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Lateral, from 12 to 02 o'clock, 5 %, within 8 inches of joint: YES

    50.5 ft. - Roots Medium Lateral, from 12 to 02 o'clock, 5 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES

    158.8 ft. - Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    158.8 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES

    219.7 ft. - Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

    224.2 ft. - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, from 12 to 05 o'clock, 30 %, within 8 inches of joint: YES

    258.4 ft. - Roots Medium Connection, from 12 to 05 o'clock, 30 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: YES

    293.4 ft. - Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
69.4TFA
379.5DAGS
219.7RFC
293.4RMC
219.7TFA
50.5TFDROOTS
258.4TFA
0MWL
224.2TF
158.8RMC
99.2TFA
258.4RMC
224.2RFC
2DAGS
50.5RML
0MWM
380.5AMH17 0037
380.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
158.8TFD
293.4TBA
0AMH17 0038
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (5)

additional_info
SC225483
custom_field_two
4
customer
LACSD
datetime
2016-02-18T23:48:58-08:00
sewer_category
GRAVITY