Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2016, 09:32 AM
  • H 1435_H 1434 _17082016_023330.mp4

Date
08/17/2016
W/O
585476
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01204
PipeID
P16307
Time
2:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3567
Sewer Name
H JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_585476_TV22034_AUG2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1435
Downstream MH
H 1434
Dir. of Survey
Downstream
Length Surveyed
299.4 ft.
Total Length
299.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 1435 to H 1434
MH: H 1435MH: H 1434downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14350 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MWL - Water Level, 10 %of cross sectional area12.9 ft. MGO - General Observation - MAG COAT 85%43.7 ft. SAV - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: YES61 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"236.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.4 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK299.4 ft. AMH - Downstream Manhole, Survey Ends - H 1434

Observation photos (1)

  • Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: YES

    43.7 ft. - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
132.3TF
61TF
196.9TF
0MWM
236.9TF
43.7SAV
0AMHH 1435
299.4MGOLATERAL AT MH 9 OCLOCK
0MGOLATERAL AT MH 3 OCLOCK
299.4AMHH 1434
164.3TF
0MWL
12.9MGOMAG COAT 85%

Properties (5)

additional_info
SC305900
custom_field_two
4
customer
LACSD
datetime
2016-08-17T02:32:38-07:00
sewer_category