Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 29, 2016, 02:07 PM
  • 14 0553_14 0552_29022016_060805.mp4

Date
02/29/2016
W/O
552346
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18647
Time
6:07 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3271
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
14
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
14 0553
Downstream MH
14 0552
Dir. of Survey
Downstream
Length Surveyed
485.3 ft.
Total Length
485.3 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2R00
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
196
Pipe schematic from manhole 14 0553 to 14 0552
MH: 14 0553MH: 14 0552downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 14 05532 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COATING 95%377.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start484 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish484 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish485.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK485.3 ft. AMH - Downstream Manhole, Survey Ends - 14 0552

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    377.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
484SSS
2.6MGOMAG COATING 95%
0MWL
2DAGS
485.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOCAPPED CONNECTION AT MH 9 O'CLOCK
377.9SSS
0MGOCAPPED CONNECTION AT MH 3 O'CLOCK
485.3AMH14 0552
0AMH14 0553
484DAGS

Properties (5)

additional_info
SC225495
custom_field_two
5
customer
LACSD
datetime
2016-02-29T06:07:48-08:00
sewer_category