Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2016, 07:34 AM
  • 14 0550_14 0549_29022016_233521.mp4

Date
02/29/2016
W/O
552346
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18643
Time
11:34 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3272
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
14
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
14 0550
Downstream MH
14 0549
Dir. of Survey
Downstream
Length Surveyed
554.2 ft.
Total Length
554.2 ft.
Structural Index
3
Structural Quick
3U00
Structural Rating
330
O&M Index
2
O&M Quick
2U00
O&M Rating
220
Overall Index
3
Overall Quick
Overall Rating
550
Pipe schematic from manhole 14 0550 to 14 0549
MH: 14 0550MH: 14 0549downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 05500 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 95%552.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish554.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0549

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
554.2AMH14 0549
0MWM
0AMH14 0550
2DAGS
0MWL
552.7DAGS
2MGOMAG COATING 95%

Properties (5)

additional_info
SC225496
custom_field_two
5
customer
LACSD
datetime
2016-02-29T23:34:54-08:00
sewer_category
GRAVITY