Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2016, 09:57 AM
  • 08 0483_08 0482 _08302016_030040.mp4

Date
08/30/2016
W/O
585990
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00007
PipeID
P00541
Time
2:57 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3647
Sewer Name
08 FRAMPTON AVENUE TRUNK
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
WO_585990_TV08086_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0483
Downstream MH
08 0482
Dir. of Survey
Downstream
Length Surveyed
490.3 ft.
Total Length
490.3 ft.
Structural Index
3
Structural Quick
3F26
Structural Rating
123
O&M Index
2
O&M Quick
2R00
O&M Rating
194
Overall Index
2
Overall Quick
Overall Rating
317
Pipe schematic from manhole 08 0483 to 08 0482
MH: 08 0483MH: 08 0482downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04830 ft. MWM - Water Mark, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start5.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"5.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.4 ft. CS - Crack Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES180.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES187.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"241.4 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES251.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES276.7 ft. CS - Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES286.8 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES289.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.9 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES316.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start339.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"389.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"439.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"478.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start483.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish488.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish488.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish490.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0482

Observation photos (10)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

    145.4 ft. - Crack Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    180.7 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    241.4 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    251.7 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

    276.7 ft. - Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    286.8 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    291.9 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    316.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

    478.3 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
483.3FL
316.6CM
241.4CS
5.1TFA
251.7CL
0MWL
2DAGS
339.3TF
0AMH08 0483
187.9TFC
137.6TFC
286.8CM
478.3FL
488.6CM
0MWM
291.9CL
276.7CS
86.9TFC
488.6DAGS
145.4CS
5.3TFA
180.7CL
490.3AMH08 0482
36.4TF
238.4TFC
389.2TFC
289.1TFC
439.7TFC

Properties (5)

additional_info
SC306086
custom_field_two
3
customer
LACSD
datetime
2016-08-30T02:57:07-07:00
sewer_category
Gravity