Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2016, 06:05 AM
  • 02 1877_02 1876_20160113_222639.mp4

Date
01/13/2016
W/O
547457
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00246
PipeID
P04235
Time
10:05 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3156
Sewer Name
02 DOUGLAS AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_547457_TV02192_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1877
Downstream MH
02 1876
Dir. of Survey
Downstream
Length Surveyed
115.7 ft.
Total Length
115.7 ft.
Structural Index
3
Structural Quick
3A00
Structural Rating
30
O&M Index
2
O&M Quick
4112
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
36
Pipe schematic from manhole 02 1877 to 02 1876
MH: 02 1877MH: 02 1876downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - 02 18770 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES58.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"62.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES66.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"72 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start83.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"110.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish115.7 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK115.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1876115.7 ft. VC - Vermin Cockroach

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    62.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    83.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

Observations (15)

DistanceCodeObservation
0MGOLATERAL AT MH 9 OCLOCK
4CM
72CM
62.1CM
0VC
115.7MGOLATERAL AT MH 3 OCLOCK
66.4TFC
0AMH02 1877
83.7TFC
58.7TFC
115.7AMH02 1876
115.7VC
0MWL
110.8CM
0MWM

Properties (5)

additional_info
SC224967
custom_field_two
3
customer
LACSD
datetime
2016-01-13T22:05:01-08:00
sewer_category
GRAVITY