Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2016, 07:29 AM
  • 22 0246_22 0245_20160106_004855.mp4

Date
01/05/2016
W/O
547395
Weather
Damp
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16528
Time
11:29 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3026
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0246
Downstream MH
22 0245
Dir. of Survey
Downstream
Length Surveyed
305.4 ft.
Total Length
305.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 22 0246 to 22 0245
MH: 22 0246MH: 22 0245downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02460 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK CAPPED0 ft. VC - Vermin Cockroach2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"50.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"53.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"80.1 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4" - FRACTURE INSIDE81.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"143.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"145.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"210 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"213.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"255.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - DEBRIS INSIDE261.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"302.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302.6 ft. MGO - General Observation - MAGNESIUM H.O. FINISH305.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0245

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
2.1SAV
302.5DAGS
213.1TFC
302.6SAV
0MWL
81.7TFC
302.6MGOMAGNESIUM H.O. FINISH
261.7TFC
255.8TFDEBRIS INSIDE
145.8TFC
210TFC
80.1TBDFRACTURE INSIDE
16.8TFC
0MWM
2.1MGOMAGNESIUM H.O. START
2.1DAGS
305.4AMH22 0245
50.8TFC
0AMH22 0246
143.4TFC
0MGOLATERAL AT MH 3 O'CLOCK CAPPED
0VC
53.8TFA

Properties (5)

additional_info
SC224619
custom_field_two
3
customer
LACSD
datetime
2016-01-05T23:29:35-08:00
sewer_category