Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2016, 08:23 AM
  • 22 0253_22 0252_20160105_014435.mp4

Date
01/05/2016
W/O
547395
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16535
Time
12:23 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3024
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0253
Downstream MH
22 0252
Dir. of Survey
Downstream
Length Surveyed
362.3 ft.
Total Length
362.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
2114
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 22 0253 to 22 0252
MH: 22 0253MH: 22 0252downstream0 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 22 02530 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 15 %of cross sectional area3 ft. MGO - General Observation - MAGNESIUM H.O. START3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start84.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"132.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"141.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"181.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"181.9 ft. VC - Vermin Cockroach222.8 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES - IN THE PIPELINE233.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - ROOTS INSIDE244.5 ft. RFJ - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES282.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"285.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"349.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"358.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358.6 ft. MGO - General Observation - MAGNESIUM H.O. FINISH362.3 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK ACTIVE362.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0252

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
362.3MGOLATERAL AT MH 3 O'CLOCK ACTIVE
358.6SAP
3MGOMAGNESIUM H.O. START
358.6MGOMAGNESIUM H.O. FINISH
3SAP
0MGOLATERAL AT MH 3 O'CLOCK ACTIVE
0AMH22 0253
181.9TFC
349.2TFA
282.2TFC
141.8TFA
181.9VC
0MWM
285.7TFC
233.3TFDROOTS INSIDE
0MGOLATERAL AT MH 9 O'CLOCK ACTIVE
222.8RFJIN THE PIPELINE
244.5RFJ
132.7TFC
362.3AMH22 0252
0VC
0MWL
84.1TFC

Properties (5)

additional_info
SC224617
custom_field_two
3
customer
LACSD
datetime
2016-01-05T00:23:02-08:00
sewer_category
GRAVITY