Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2016, 06:08 AM
  • 22 0258_22 0257_20160104_234655.mp4

Date
01/04/2016
W/O
547395
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16540
Time
10:08 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3024
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0258
Downstream MH
22 0257
Dir. of Survey
Downstream
Length Surveyed
390.4 ft.
Total Length
390.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
3112
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 22 0258 to 22 0257
MH: 22 0258MH: 22 0257downstream0 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02582.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START36.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"74.1 ft. VC - Vermin Cockroach74.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"80.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start80.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish104.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"128.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"168.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"171.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"228.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"232.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"281.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"299.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"323.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"352.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES369.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"370.3 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR372.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4" - ROOTS IMSIDE388.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388.6 ft. MGO - General Observation - MAGNESIUM H.O. FINISH390.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0257

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    80.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    370.3 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

Observations (27)

DistanceCodeObservation
74.1VC
299.5TF
390.4AMH22 0257
80.8SAP
0MGOLATERAL AT MH 9 O'CLOCK ACTIVE
36.6TF
104.5TF
128.8TFC
2.1SAV
232.8TF
369.2TF
388.6MGOMAGNESIUM H.O. FINISH
352.4RFJ
228.9TFC
171.8TFC
0MWM
323.6TFC
0MWL
80.8SAV
0AMH22 0258
168.5TF
388.5SAP
372.8TFAROOTS IMSIDE
370.3RMJ
74.1TFC
281.8TFC
2.1MGOMAGNESIUM H.O. START

Properties (5)

additional_info
SC224617
custom_field_two
3
customer
LACSD
datetime
2016-01-04T22:08:48-08:00
sewer_category
GRAVITY