Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2016, 11:22 AM
  • 22 0260_22 0259_20160104_043300.mp4

Date
01/04/2016
W/O
547395
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16542
Time
3:22 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3023
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0260
Downstream MH
22 0259
Dir. of Survey
Downstream
Length Surveyed
183 ft.
Total Length
183 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 22 0260 to 22 0259
MH: 22 0260MH: 22 0259downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 22 02602.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAGNESIUM H.O. START30.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"72.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"72.9 ft. VC - Vermin Cockroach115.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"124.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"179.8 ft. MGO - General Observation - MAGNESIUM H.O. FINISH179.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish179.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish183 ft. AMH - Downstream Manhole, Survey Ends - 22 0259183 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK MADE

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
2.3SAP
179.8MGOMAGNESIUM H.O. FINISH
183AMH22 0259
0MWL
0MWM
115.2TFA
2.3DAGS
2.3MGOMAGNESIUM H.O. START
30.1TFC
183MGOLATERAL AT MH 3 O'CLOCK MADE
0MGOLATERAL AT MH 9 O'CLOCK CAPPED
179.8DAGS
179.8SAP
0AMH22 0260
124.7TFC
72.9VC
72.8TFC

Properties (5)

additional_info
SC224615
custom_field_two
3
customer
LACSD
datetime
2016-01-04T03:22:43-08:00
sewer_category
GRAVITY