Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2016, 09:46 AM
  • 22 0240_22 0239_20160106_025841.mp4

Date
01/06/2016
W/O
547395
Weather
Damp
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16522
Time
1:46 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3026
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0240
Downstream MH
22 0239
Dir. of Survey
Downstream
Length Surveyed
236.9 ft.
Total Length
236.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 0240 to 22 0239
MH: 22 0240MH: 22 0239downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 02400 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE0 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. VC - Vermin Cockroach2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAGNESIUM H.O. START2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start46.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"49.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"98.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"101.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"150.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"153.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"210.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"233.3 ft. MGO - General Observation - MAGNESIUM H.O. FINISH233.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish233.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish236.8 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE236.9 ft. AMH - Downstream Manhole, Survey Ends - 22 0239236.9 ft. VC - Vermin Cockroach

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0AMH22 0240
0MWL
236.9AMH22 0239
233.3MGOMAGNESIUM H.O. FINISH
46.1TFC
210.9TFC
0MGOLATERAL AT MH 9 O'CLOCK ACTIVE
233.3DAGS
98.3TF
101.4TFC
233.3SAV
150.3TFC
236.9VC
153.5TFC
0MWM
49.1TFC
236.8MGOLATERAL AT MH 9 O'CLOCK ACTIVE
2.3SAV
2.3MGOMAGNESIUM H.O. START
0.1VC
2.3DAGS

Properties (5)

additional_info
SC224619
custom_field_two
3
customer
LACSD
datetime
2016-01-06T01:46:30-08:00
sewer_category
GRAVITY