Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2016, 09:34 AM
  • 22 0241_22 0240_20160106_024509.mp4

Date
01/06/2016
W/O
547395
Weather
Damp
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16523
Time
1:34 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3026
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0241
Downstream MH
22 0240
Dir. of Survey
Downstream
Length Surveyed
167.4 ft.
Total Length
167.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 22 0241 to 22 0240
MH: 22 0241MH: 22 0240downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK MADE0 ft. AMH - Upstream Manhole, Survey Begins - 22 02410.1 ft. VC - Vermin Cockroach2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"21.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"39.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"79.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"112.9 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area, Start112.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"131.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"141.1 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area, Finish163.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish163.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish163.8 ft. MGO - General Observation - MAGNESIUM H.O. FINISH167.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0240167.4 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE167.4 ft. VC - Vermin Cockroach

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    163.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (22)

DistanceCodeObservation
0MWL
167.4AMH22 0240
0.1VC
163.8SAV
163.8DAGS
131.1TFC
2.1DAGS
79.1TFC
2.1MGOMAGNESIUM H.O. START
0MWM
163.8MGOMAGNESIUM H.O. FINISH
39.1TFC
0MGOLATERAL AT MH 3 O'CLOCK MADE
0AMH22 0241
112.9MWLS
167.4MGOLATERAL AT MH 9 O'CLOCK ACTIVE
167.4VC
112.9TFC
141.1MWLS
18.1TFC
21.1TFC
2.1SAV

Properties (5)

additional_info
SC224619
custom_field_two
3
customer
LACSD
datetime
2016-01-06T01:34:01-08:00
sewer_category