Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2016, 01:03 PM
  • 22 0337_22 0263_20160104_061410.mp4

Date
01/04/2016
W/O
547395
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16546
Time
5:03 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3023
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0337
Downstream MH
22 0263
Dir. of Survey
Downstream
Length Surveyed
210.8 ft.
Total Length
210.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
2113
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 22 0337 to 22 0263
MH: 22 0337MH: 22 0263downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 03370 ft. MGO - General Observation - BULKHEAD AT MH0 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.7 ft. MGO - General Observation - MAGNESIUM H.O. START24.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"27.9 ft. VC - Vermin Cockroach60.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"73.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"109.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"121.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"170.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"194.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"195.6 ft. RFJ - Roots Fine Joint, from 10 to 04 o'clock, within 8 inches of joint: YES202.2 ft. RFJ - Roots Fine Joint, from 12 to 01 o'clock, within 8 inches of joint: YES207.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish207.4 ft. MGO - General Observation - MAGNESIUM H.O. FINISH207.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish210.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0263

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
0MWM
109.1TFC
0AMH22 0337
24.6TFC
2.7DAGS
195.6RFJ
0MGOBULKHEAD AT MH
207.4SAP
0MGOLATERAL AT MH 3 O'CLOCK ACTIVE
210.8AMH22 0263
27.9VC
194.4TFA
2.6SAP
60.9TFA
2.7MGOMAGNESIUM H.O. START
73.1TF
207.4MGOMAGNESIUM H.O. FINISH
121.7TFC
202.2RFJ
207.4DAGS
170.2TFC
0MWL

Properties (5)

additional_info
SC224615
custom_field_two
3
customer
LACSD
datetime
2016-01-04T05:03:16-08:00
sewer_category