Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2016, 09:03 AM
  • 22 0242_22 0241_20160106_023339.mp4

Date
01/06/2016
W/O
547395
Weather
Damp
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16524
Time
1:03 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3026
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_547395_TV22016_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0242
Downstream MH
22 0241
Dir. of Survey
Downstream
Length Surveyed
396.7 ft.
Total Length
396.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
1
O&M Quick
2113
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 22 0242 to 22 0241
MH: 22 0242MH: 22 0241downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02420 ft. MWL - Water Level, 15 %of cross sectional area0 ft. VC - Vermin Cockroach2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START3.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES25.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"53.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"83.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"123.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"138.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"172.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"196.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"215.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"252.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"253.3 ft. VC - Vermin Cockroach273.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"294.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"322.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"346.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"392.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish392.9 ft. MGO - General Observation - MAGNESIUM H.O. FINISH393 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish396.7 ft. VC - Vermin Cockroach396.7 ft. AMH - Downstream Manhole, Survey Ends - 22 0241396.7 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK MADE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    3.8 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    393 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (28)

DistanceCodeObservation
252.2TFA
393SAV
83.5TFC
294.7TFC
396.7VC
253.3VC
196.8TFC
215.5TF
3.8CL
0MWM
123.7TFA
396.7AMH22 0241
392.9DAGS
392.9MGOMAGNESIUM H.O. FINISH
2.1DAGS
0AMH22 0242
138.5TFC
53.1TFC
346.7TFC
25.7TFC
322.4TF
396.7MGOLATERAL AT MH 3 O'CLOCK MADE
2.1SAV
2.1MGOMAGNESIUM H.O. START
273.3TFC
0MWL
172.6TFC
0VC

Properties (5)

additional_info
SC224619
custom_field_two
3
customer
LACSD
datetime
2016-01-06T01:03:31-08:00
sewer_category
GRAVITY