Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 31, 2015, 08:11 AM
  • 22 0286_22 0285_20151231_002459.mp4

Date
12/31/2015
W/O
547382
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16572
Time
12:11 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3021
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_547382_TV22014_JAN2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0285
Downstream MH
22 0286
Dir. of Survey
Upstream
Length Surveyed
318.2 ft.
Total Length
318.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
2113
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 22 0285 to 22 0286
MH: 22 0285MH: 22 0286upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 02860 ft. VC - Vermin Cockroach3.5 ft. MGO - General Observation - MAGNESIUM H.O. FINISH3.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish21.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"53.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"69.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"118.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"139 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"150.6 ft. VC - Vermin Cockroach150.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"179.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"272.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"316 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start316 ft. MGO - General Observation - MAGNESIUM H.O. START316 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start318.2 ft. MWL - Water Level, 10 %of cross sectional area318.2 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE318.2 ft. AMH - Downstream Manhole, Survey Begins - 22 0285318.2 ft. VC - Vermin Cockroach318.2 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    314.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (22)

DistanceCodeObservation
167.6VC
314.7MGOMAGNESIUM H.O. FINISH
314.7SAP
179.2TFA
45.6TFA
0MWL
296.7TFA
2.2SAP
199.8TFA
2.2MGOMAGNESIUM H.O. START
248.4TFA
318.2AMH22 0286
167.6TFA
2.2DAGS
0MGOLATERAL AT MH 9 O'CLOCK ACTIVE
264.3TFA
318.2VC
0AMH22 0285
0VC
314.7DAGS
138.9TFA
0MWM

Properties (5)

additional_info
SC224613
custom_field_two
3
customer
LACSD
datetime
2015-12-31T00:11:36-08:00
sewer_category
GRAVITY