Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2016, 10:35 AM
  • 02 1487_02 1486 _20160801_045143.mp4

Date
08/01/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03932
Time
3:35 AM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3669
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
V
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1486
Downstream MH
02 1487
Dir. of Survey
Upstream
Length Surveyed
208.4 ft.
Total Length
208.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1486 to 02 1487
MH: 02 1486MH: 02 1487upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETED0 ft. OBZ - Obstacles Other, 10 %of cross sectional area, at 06 o'clock - POSSIBLE SEWER DRAIN SNAKE2.8 ft. CM - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES28.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"80.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"130.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"158.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"162 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES162 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"208.4 ft. MWM - Water Mark, 10 %of cross sectional area208.4 ft. MGO - Reversal Inspection208.4 ft. AMH - Downstream Manhole, Survey Begins - 02 1486208.4 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (3)

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"

    46.4 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"

  • Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    205.6 ft. - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Obstacles Other, 10 %of cross sectional area, at 06 o'clock - POSSIBLE SEWER DRAIN SNAKE

    208.4 ft. - Obstacles Other, 10 %of cross sectional area, at 06 o'clock - POSSIBLE SEWER DRAIN SNAKE

Observations (13)

DistanceCodeObservation
46.4CM
0MWM
205.6CM
46.4TFC
77.8TF
128.3TFC
0MGO
0AMH02 1486
208.4MSAREVERSAL COMPLETED
208.4OBZPOSSIBLE SEWER DRAIN SNAKE
0MWL
50.3TF
180.3TFC

Properties (5)

additional_info
SC305549
custom_field_two
4
customer
LACSD
datetime
2016-08-01T03:35:19-07:00
sewer_category
Gravity