Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 2, 2016, 10:37 AM
  • 02 1467_02 1466 _20160802_044953.mp4

Date
08/02/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03911
Time
3:37 AM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3670
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1467
Downstream MH
02 1466
Dir. of Survey
Downstream
Length Surveyed
209.9 ft.
Total Length
209.9 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 1467 to 02 1466
MH: 02 1467MH: 02 1466downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14670 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"23.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"33.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"44.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES51 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"60.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"75.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"84.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"99.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"114.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"127 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"139.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"167 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"176.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"176.5 ft. FC - Fracture Circumferential, from 06 to 10 o'clock, within 8 inches of joint: YES179.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"180.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES190.5 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start207.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish207.8 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish209.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1466209.9 ft. MGO - General Observation - CONNECTION AT THE MH O'CLOCK ACTIVE209.9 ft. MGO - General Observation - CONNECTION AT THE MH O'CLOCK ACTIVE

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    84.6 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    167 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Fracture Circumferential, from 06 to 10 o'clock, within 8 inches of joint: YES

    176.5 ft. - Fracture Circumferential, from 06 to 10 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    207.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (27)

DistanceCodeObservation
84.6TF
207.8DAGS
60.2TFC
207.8DSGV
23.8TFA
75.3TFA
167TB
127TFA
209.9AMH02 1466
51TFC
0AMH02 1467
99.5TFC
114.9TFA
176.5FC
33.2TFC
180.1CL
190.5DSGV
8.8TFA
0MWM
209.9MGOCONNECTION AT THE MH O'CLOCK ACTIVE
0MWL
179.1TFC
176.1TFC
209.9MGOCONNECTION AT THE MH O'CLOCK ACTIVE
44.2CL
2.7DAGS
139.3TFC

Properties (5)

additional_info
SC305550
custom_field_two
4
customer
LACSD
datetime
2016-08-02T03:37:00-07:00
sewer_category
Gravity