Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2016, 11:33 AM
  • 02 1484_02 1483 _20160801_060457.mp4

Date
08/01/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03929
Time
4:33 AM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3669
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1484
Downstream MH
02 1483
Dir. of Survey
Downstream
Length Surveyed
272.2 ft.
Total Length
272.2 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
8
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 1484 to 02 1483
MH: 02 1484MH: 02 1483downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14840 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start3.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"8.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"24 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES33.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"60.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"88.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"95.9 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES112.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"137.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"137.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES147.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES164.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"188.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"229.3 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES229.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"272.1 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish272.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE272.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1483

Observation photos (7)

  • Deposits Settled Gravel,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    8.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    95.9 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    137.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES

    147.9 ft. - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    188.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    229.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"

Observations (22)

DistanceCodeObservation
24DSGV
188.9TFC
137.3TFC
8.5TFC
137.8CL
3.8TFC
33.3TFC
0MWL
2DSGV
272.2MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
60.8TFC
0AMH02 1484
272.1DSGV
0MWM
164.6TFC
95.9CM
147.9FC
229.3CC
272.2AMH02 1483
112.7TFC
229.3TF
88.3TF

Properties (5)

additional_info
SC305549
custom_field_two
3
customer
LACSD
datetime
2016-08-01T04:33:00-07:00
sewer_category